How to Quickly Resolve RS485 Network Communication Issues

2026-05-11

The advantages of the RS-485 bus are well-established, and isolation RS-485 modules are typically employed to ensure communication stability. However, during actual RS-485 network deployment, issues such as communication failures, error occurrences, or damaged RS-485 transceivers may arise to varying degrees. This article provides an in-depth analysis of the underlying causes of these networking issues.

When a communication error occurs or communication fails, first determine whether the application falls under the application scenarios listed in Table

Table 1 RS-485 Bus Application Scenarios

number

Application Status

Possible reasons

1

There is a terminal resistor on the bus, and the threshold level of the RS-485 transceiver used is ± 200mV

Terminal resistance causes the idle state AB differential voltage to be within the threshold level

2

Nodes have added pull-up and pull-down resistors, for example, adding 680 Ω pull-up and pull-down resistors each. There are 10 nodes on the bus

The resistance value of the up and down resistors is too small, exceeding the driving capacity of the chip

3

Immediately send or receive data after CON switching

The delay time for switching between sending and receiving states is too short

4

The 5V module uses a 3.3V level MCU for power supply

Level mismatch

Table 1 outlines four application scenarios corresponding to issues involving terminal resistance, pull-up/pull-down resistors, control pins, and logic input level. A detailed analysis follows below.

1、Terminal resistor issue

If a terminal resistor is connected to the RS-485 bus and the RS-485 transceiver uses a threshold level of ±200 mV, the abnormal phenomena described in Table 2 may occur.

Table 2 Abnormal phenomena caused by terminal resistance

number

abnormal phenomenon

1

Single boards can communicate during normal testing, but cannot communicate with each other after networking or with other devices

2

The single board test did not pass, but after replacing the RS-485 module, it returned to normal. There is a certain proportion of failures

3

The single board communicates normally with the upper computer through the RS-232/485 bidirectional converter (as shown in Figure 1);

Two single boards cannot communicate normally;

If RS-232/485 bidirectional converters are added to two boards, communication will be normal.

1.jpg

Figure 1 RS232/485 bidirectional converter

The cause of anomalies due to terminal resistance:

The RS-485 transceiver has a reception threshold level of ±200 mV. Specifically, when the differential voltage between AB exceeds +200 mV, the output is high; when it falls below-200 mV, the output is low; when the voltage falls within ±200 mV, the output state becomes indeterminate—it may output either a high level (indicating normal communication) or a low level (indicating communication anomaly). Consequently, when the bus is idle and the AB differential voltage lies within this threshold range, anomalies may occur with a certain probability.

Table 2 Phenomenon 1 Analysis: The board communicates normally, but after networking, the presence of a termination resistor on the RS-485 bus causes the differential voltage on the bus to remain within the threshold level during idle states, resulting in communication anomalies. When this occurs, first verify whether a termination resistor is present on the bus.

Table 2 Phenomenon 2 Analysis: During single-board testing, when either the board or its communicating device is connected with a terminal resistor, communication anomalies may occur with a certain probability if the differential voltage between AB falls within the threshold level.

Table 2: Analysis of Phenomenon 3: This phenomenon is also caused by terminal resistance. The AB pins of the RS-232/485 bidirectional converter (as shown in Figure 1) typically incorporate small-value pull-up/pull-down resistors (e.g., 560Ω). When using the RS-232/485 bidirectional converter for communication, the voltage during the RS-485 bus idle state is determined by voltage division between the pull-up/pull-down resistor and the terminal resistance. In this case, the AB differential voltage during idle exceeds 200 mV, causing the RS-485 transceiver to output a stable high level without triggering communication errors. Figure 2 illustrates communication between two RSM485PCHTs with a 60Ω resistor connected between AB and the RS-232/485 bidirectional converter's test waveform; the idle voltage measures 520 mV, preventing errors. Figure 3 shows the test waveform with a 60Ω resistor between AB during communication between two RSM485PCHTs, revealing an AB differential voltage of 40 mV during idle—within the threshold range—but still potentially causing communication errors.

2.jpg

Figure 2: Add two 120Ω resistors between AB and install an RS-232/485 bidirectional converter.

3.jpg

Figure 3: Only two 120Ω resistors are added between AB.

There are primarily three solution methods, as detailed in Table 3:

 Table 3 – Solutions to Terminal Resistance Issues

number

solution

1

Remove the terminal resistor. When there is no signal reflection problem on the RS-485 bus, no terminal resistor can be added

2

Using transceivers with output power pins such as RSM485PCHT, adjust the voltage value during idle state by adding a smaller pull-up and pull-down resistor externally

3

Use modules with threshold levels ranging from -40mV to -200mV, such as RSM485ECHT bus

2、Pull-up and pull-down resistor issues: Insufficient parallel resistance values may cause the following phenomena, as shown in Table 4.

Table 4 Abnormal phenomena caused by pull-up and pull-down resistors

number

abnormal phenomenon

1

When the number of nodes on the bus increases to a certain level, the nodes on the bus cannot communicate normally. After reducing the number of nodes, it returns to normal.

 The aforementioned issue arises from the excessively low resistance values of the pull-up and pull-down resistors, which exceed the chip's load driving capacity. As shown in Table 5, when two 120Ω resistors are connected between AB on the RSM485PCHT, the relationship between the combined pull-resistance value and the low-level output differential voltage is illustrated. If the parallel resistance value of the pull-up and pull-down resistors is less than 51Ω, the chip may function normally, but the output signal exceeds-200mV, potentially causing communication errors or complete failure. Insufficient pull-resistance values lead to excessive power consumption and severe heat generation in the RS-485 transceiver, increasing the risk of overheating protection activation or component damage. To ensure communication reliability, the combined resistance value of pull-up and pull-down resistors should generally exceed 375Ω.

Table 5 Driving voltages for different pull-up and pull-down resistor values

number

 Resistance values of up and down resistors(Ω)  (Pull up A, pull down B)

A-RGND  (V)

B-RGND (V)

  A-B(V)

1

390

1.474

3.046

-1.572

2

300

1.504

2.998

-1.494

3

200

1.569

2.896

-1.327

4

100

1.751

2.615

-0.864

5

51

2.071

2.183

-0.112

3、Control Foot Problem

Since the transmit-receive switching involves a certain delay, an additional delay period (e.g., at least 25 μs for RSM485PCHT) should be introduced before sending or receiving data to ensure the RS-485 transceiver is properly configured for transmission or reception.

4、For logic input-side issues

 the MCU voltage level must match the RS-485 transceiver's input logic level; specifically, if the MCU operates at a 5V logic level, an RSM-series isolation module with a 5V power supply should be used.